We supply spare parts and equipment of truck-mounted drilling rig,trailer-mounted drilling rig, work over rig ,electrical drilling rig etc. Keep long business cooperation relationship with API Manufacturers BOMCO,LSNOW,SICHUANG HONGHUA,SJ PETRO,RG PETRO, BPM(Beijing Petroleum Machinery Factory), GGPMF, RONGSHENG,SHENKAI,BEIJING PSK, RENQIU BOKE,HYSUN MARINE etc.
Contact us
SKYPE:spareparts1960
Mobile/WhatsApp:0086-189-5407-9939
Insulating Gloves to IEC60903 |
Workplace safety can mean different things for different environments. Whatever safety means for your role, dhparts.com can help you to achieve it. dhparts.com provides high-quality, dependable products you can trust to keep employees and work sites safe.
We sell Electrical Insulating Gloves to IEC60903 with class 00,0,1,2,3,4.Types availabe Latex Gloves & Composite Gloves.Maximum working voltage from 500V to 36,000V.
Insulating Gloves to IEC60903
Electrical Insulating Gloves Class 0, Class 1, Class 2, Class 3, Class 4
There are 2 main types of insulating gloves
i) Latex Gloves provide high dielectric performance and must be used with leather over gloves for mechanical protection
ii) Composite Gloves provide superior mechanical protection against punctures and tears eliminating the need for over-gloves. Wearing suitable PPE to protect electrical engineers, cable jointers and linesmen against dangers posed by exposure to electric cables and circuits is essential. Insulating gloves must be flexible and durable with high dielectric strength compliant with IEC 60903. Insulating rubber gloves conform to IEC 60903 standard. IEC 60903 standard insulating rubber gloves are subject to electrical, mechanical resistance and aging tests - composite and rubber insulating gloves are available to prevent against electric shock hazards.
Typical applications include:
Low voltage and live-working up to 1kV (Class 0 Insulating Gloves)
Live line working on overhead lines (Class 1, 2, 3, 4 Insulating Gloves)
Electrical switching
Operating underground moling machines
Class
|
Maximum Use Voltage (AC)
|
Proof Tested (VAC)
|
Proof Tested (VDC)
|
00
|
500
|
2,500
|
4,000
|
0
|
1,000
|
5,000
|
10,000
|
1
|
7,500
|
10,000
|
20,000
|
2
|
17,000
|
20,000
|
30,000
|
3
|
26,500
|
30,000
|
40,000
|
4
|
36,000
|
40,000
|
60,000
|